Pressure Vacuum Breaker Backflow Preventer Troubleshooting

 
Symptom Probable Cause
Air inlet valve does not open as gauge drops to 0.0 psid. Air inlet disc stuck to seat.
Air inlet valve does not open and differential on gauge will not drop. Leaking No. 1 shut-off valve
Air inlet opens below 1.0 psid. Dirty or damaged air inlet disc.
Scale buildup on disc or bonnet.
Check valve opens below 1.0 psid. Dirty or damaged check disc or seat o-ring.
Damaged seat.